User Manual of EM730/EM730E Series Inverter
59
5.5
Start and Stop Control
Functio
n code
Function code
name
Parameter description
Default
setting
Attribute
F00.02
Options of
command
source
0: keyboard control
1: Terminal control
2: Communication control
0
〇
F00.02=0: keyboard control
The start and stop of the inverter are controlled by the RUN key, STOP key on the keyboard.
In the case of no trip protection, press the RUN key to enter the running status. If the green LED
indicator above the RUN key is normally ON, it indicates that the inverter is running. If this
indicator is flickering, it indicates that the inverter is in the status of deceleration to stop.
F00.02=1: terminal control
The inverter start and stop are controlled by the start and stop control terminals defined by
the function code F02.00 to F02.04. Terminal control is dependent on F00.03.
F00.02=2: communication control
The inverter start and stop are controlled by the host through the RS485 communication
port.
Function
code
Function code
name
Parameter description
Default
setting
Attribute
F04.00 Start-up method
0: direct start
1: start of speed tracking
0
〇
F04.00=0: direct start
The inverter is started at the starting frequency, following the DC braking (not suitable
when F04.04=0) and pre-excitation (not suitable when F04.07=0). The starting frequency will
change to the set frequency after the holding time.
F04.00=1: start with speed tracking
The inverter is smoothly started at the current rotating frequency of the motor, following
the speed tracking.
Function
code
Function code
name
Parameter description
Default
setting
Attribute
F04.19 Stop mode
0: Slow down to stop
1: Free stop
0
〇
F04.19=0: deceleration to stop
The motor decelerates to stop according to the set deceleration time [default setting: based
on F00.15 (deceleration time 1)].
F04.19=1: free stop
When there is a valid stop command, the inverter will stop output immediately, and the
motor will freely coast to stop. The stop time depends on the inertia of the motor and load.