User Manual of EM730/EM730E Series Inverter
211
1: memory (from the moment of
stop)
Tens place:
Power-down
memory options
0: no memory (from the first
segment)
1: Memory (from the
power-down moment)
The PLC stop memory is to record the current simple PLC running times (F18.10), running
stage (F18.11), and running time at the current stage (F18.12). The inverter will continue to run
from the memory stage during next operation. If you choose no memory, the PLC process will
be performed every time the inverter is started.
The PLC power-down memory is to record the current simple PLC running times (F18.10),
running stage (F18.11), and running time at the current stage (F18.12) before the memory is
powered off. The inverter will continue to run from the memory stage when the inverter is
powered on again. If you choose no memory, the PLC process will be performed every time the
inverter is powered on.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F08.18
Simple PLC time
unit
0: s (second)
1: min (minute)
0
●
In order to meet different working conditions, the running time involved in the PLC
function is set to a numerical value. Its specific meaning needs to be set in conjunction with the
simple PLC time unit (F08.18). At present, there are two types of unit: second and minute.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F08.19
Setting of the first
segment
Ones place:
Running
direction options
0: forward
1: reverse
Tens place:
Acceleration and
deceleration time options
0: acceleration and
deceleration time 1
1: acceleration and
deceleration time 2
2: acceleration and
0
●