of F14.52, the
weaker the
speed PID
regulation is.
Function code
F14.77
Acceleration/deceler
ation time options of
motor 2
0: the same as motor 1
1: acceleration and
deceleration time 1
2: acceleration and
deceleration time 2
3: acceleration and
deceleration time 3
4: acceleration and
deceleration time 4
0
〇
F14.77=0
: the acceleration/deceleration time of the motor 2 is the same as that of the motor
1. For details, see the description of the function codes F15.03 to F15.09;
F14.77=1/2/3/4
: the acceleration/deceleration time of the motor 2 is fixed as the
acceleration/deceleration time 1/2/3/4, corresponding to the function codes F00.14,
F00.15/F15.03, F15.04/F15.05, F15.06/F15.07 and F15.08, respectively.
Function
code
Function code name
Parameter description Unit
Default
setting
Attribute
F14.78 Maximum frequency of motor 2 20.00~600.00
Hz
50
〇
F14.79
Upper frequency limit of motor
2
Lower limit frequency
F00.19 to maximum
frequency F14.78
Hz
50
●
See F00.16 and F00.18
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F14.80
V/F curve setting of
motor 2
0: straight line V/F
1: multi-point broken line
V/F
2: 1.3-power V/F
3: 1.7-power V/F
4: square V/F
5: VF complete separation
mode (Ud = 0, Uq = K * t
= voltage of separation
voltage source)
6: VF semi-separation
0
〇