User Manual of EM730/EM730E Series Inverter
272
input terminals (VX1 to VX8), of which the functions and usages are basically the same as those
of the actual input terminals. Differences are described below. For their similarities, refer to the
parameter description of Function Parameter Group of Input Terminal of F02 Group.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F17.00
VX1 virtual input
function options
The same as the digital input
terminal function options of the
F02 group. See the function list of
the digital multi-function input
terminal in Table 7-2.
0
〇
F17.01
VX2 virtual input
function options
0
〇
F17.02
VX3 virtual input
function options
0
〇
F17.03
VX4 virtual input
function options
0
〇
F17.04
VX5 virtual input
function options
0
〇
F17.05
VX6 virtual input
function options
0
〇
F17.06
VX7 virtual input
function options
0
〇
F17.07
VX8 virtual input
function options
0
〇
F17.08
Virtual input
positive/negative logic
D7 D6 D5 D4 D3 D2 D1 D0
000
00000
〇
VX
7
VX
6
VX
6
VX
5
VX
4
VX
3
VX
2
VX
1
0: positive logic, valid in the
closed state/invalid in the open
state
1: Negative logic, invalid in the
closed state/valid in the open state
F17.11 VX1 valid delay time 0.000-30.000
s
0.000
●
F17.12
VX1 invalid delay
time
0.000-30.000
s
0.000
●
F17.13 VX2 valid delay time 0.000-30.000
s
0.000
●
F17.14
VX2 invalid delay
time
0.000-30.000
s
0.000
●
F17.15 VX3 valid delay time 0.000-30.000
s
0.000
●
F17.16
VX3 invalid delay
time
0.000-30.000
s
0.000
●
F17.17 VX4 valid delay time 0.000-30.000
s
0.000
●
F17.18
VX4 invalid delay
time
0.000-30.000
s
0.000
●