User Manual of EM730/EM730E Series Inverter
171
the multi-function output ports will be in the invalid status. If the selected function is enabled,
the electronic switch will be ON, and the multi-function output ports will be in the valid status.
The open collector can be powered on internally or by an external power supply (12-30V).
The relay output is from the internal
relay of the inverter. The relay has one set of
normally open contacts and one set of
normally closed contacts. When the selected
function is disabled, the EB-EC is normally
closed and EA-EC is normally open. When
the selected function is enabled, the internal
relay coil will be powered on, the EB-EC
will be disconnected, and the EA-EC will be
engaged. See Fig. 7-12.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F03.05
Options of
output signal
type
D7
D6
D5
D4
D3 D2 D1 D0
0*0
〇
*
*
*
*
*
R1 * Y1
0: level
1: single pulse
Function i output
Level output
Pulse output width
Single pulse
output
Valid
Invalid
Valid
Invalid
Valid
Invalid
Fig. 7-13 Schematic Diagram of Level and Single Pulse Output of Digital Output Terminal
EA
EB
EC
Relay E coil
Fig. 7-12 Relay Contacts