![Sinee EM730 Series Скачать руководство пользователя страница 87](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544087.webp)
User Manual of EM730/EM730E Series Inverter
87
factor of
stator resistor
of
asynchronous
motor
F06.77
Low speed
correction
factor of
rotor resistor
of
asynchronous
motor
10.0~500.0
%
100.0
●
F06.78
Slip gain
switching
frequency of
asynchronous
motor
0.10~Fmax
Hz
5.00
〇
F07
Protection function setting group
F07.00
Protection
shield
E20
*
E13
E06
*
E04
E07
E08
0*0
0*000
〇
0: valid protection
1: shielded protection
F07.01
Motor
overload
protection
gain
0.20 - 10.00
1.00
●
F07.02
Motor
overload
pre-alarm
coefficient
50 - 100
%
80
●
F07.06
Bus voltage
control
options
Ones place: Instantaneous stop/no-stop function options
0: Invalid
1: deceleration
2: deceleration to stop
Tens place: Overvoltage stall function options
0: Invalid
1: valid
10
〇
F07.07
Voltage of
overvoltage
stall control
110.0 - 150.0 (380V, 100.0=537V)
%
131.0(703V)
〇
F07.08
Instantaneous
stop/no-stop
operating
voltage
60.0 to instantaneous stop/no-stop recovery voltage (100.0
= standard bus voltage)
%
76.0
〇