User Manual of EM730/EM730E Series Inverter
66
Default
setting
Function code settings before delivery, or values after parameter restoration
(F12.14=1). This is mainly described by the following three categories.
Number (e.g.
50.00)
Refer to each power segment. The function code is set to
the current value by default.
Depending on
the motor type
The default setting of this function code varies based on
the power segments.
XXX
The default setting of this function code varies based on
the power segments and batches.
Attribute
Change attribute of the function code (permission and condition of change),
as described below:
●
Changeable in running: The current function code can be
changed in any status.
〇
Non-changeable in running: The current function code can be
changed except in the running status.
×
Read-only: The current function code cannot be changed in
any status.
6.2
Table of functional parameters
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F00
Basic function parameter group
F00.00 Reserved
F00.01 Drive control mode of motor 1
0: V/F control (VVF)
1: Speed sensorless vector control (SVC)
0
〇
F00.02 Options of command source
0: keyboard control (LOC/REM indicator: ON)
1: terminal control (LOC/REM indicator: OFF)
2: communication control (LOC/REM indicator:
flicker)
0
〇
F00.03 Options of terminal control mode
0: terminal RUN (running) and F/R (forward/reverse)
1: terminal RUN (forward) and F/R (reverse)
2: terminal RUN (forward), Xi (stop) and F/R
(reverse)
3: terminal RUN (running), Xi (stop) and F/R
(forward/reverse)
0
〇
F00.04
Options of main frequency source
A
0: digital frequency setting F00.07
1
:
AI1
2
:
AI2
3: retention
4: retention
5: high frequency pulse input (X5)
6: main frequency communication setting
8
〇