User Manual of EM730/EM730E Series Inverter
173
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F03.08
Output status
control in jog
D7 D6 D5 D4
D3
D2
D1
D0
00000
〇
*
*
* REV
FDT
2
FDT
1
FAR RUN
0: valid in jogging
1: invalid in jogging
It is usually not necessary for DO to output certain statuses during jog running. The
corresponding output can be shielded by setting the corresponding bit of this function code to 1.
If F03.08=xxx1x is set and the FAR output is valid, the actually selected output terminal will not
output the active level.
This function code is subject to bit operation. For specific settings, refer to the description
of the function code F02.15. Table 7-7
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F03.09
Y1 valid delay time
0.000-30.000
s
0.000
●
F03.10
Y1 invalid delay time
0.000-30.000
s
0.000
●
F03.13
R1 valid delay time
0.000-30.000
s
0.000
●
F03.14
R1 invalid delay time
0.000-30.000
s
0.000
●