User Manual of EM730/EM730E Series Inverter
206
protection retries will be carried out based on the last count.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F07.19
Action
option 1 of
protection
E21
E16
E15
E14
E13
*
E08
E07
000
00*00
〇
0: free stop
1: stop according to stop mode
F07.20
Action
option 2 of
protection
E28
E27
*
E23
00*0
〇
0: free stop
1: stop according to stop mode
With regard to some protections, the action mode of the inverter can be selected via this
function code. The inverter will stop running freely when the corresponding bit is set to 0 and
according to the stop mode (F04.19) when the corresponding bit is set to 1.
These two function codes are subject to bit operation. You only need to set the
corresponding bit to 0 or 1. As shown in the table below:
Table 7-11 Detailed Definition of Protection Action Bits
F07.19
E21
E16
E15
E14
E13
*
E08
E07
F07.20
*
*
*
*
E28
E27
*
E23
Correspond
ing bit
7
6
5
4
3
2
1
0
Settings
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
For example: To stop the inverter according to the stop mode (F04.19) after the
E08
and
E13
protection is enabled, you only need to set the 1
st
bit corresponding to E08 and the 3
rd
bit
corresponding to
E13
to 1. That is, F07.19=xxx x1x1x.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F07.21
Options of load loss
protection
0: invalid 1: valid
0
●
F07.22 Load loss detection level 0.0-100.0
%
20.0
●
F07.23 Load loss detection time 0.0 - 60.0
s
1.0
●
F07.24
Options of load loss
protection action
0: trip protection, free stop
1: trip protection, stop
according to stop mode
2: Continue to run, with DO
status output
1
〇
When the off-load protection is valid (F07.21=1), the inverter will be in the running status
without DC braking, and the output current is below the off-load detection level (F07.22) and
maintained for the off-load detection time (F07.23), the inverter will be in the off-load status.
Specific processing depends on F07.24.