The PID setting depends on the digital PID setting (F09.01), and the specific percentage is
F09.01/F09.03 * 100.00%.
F09.00=1:AI1
F09.00=2:AI2
For the details of AI1 to AI2, refer to the description of F00.04. For PID setting, the
percentage is directly given, and the maximum output is 100.00%.
F09.00=5: PULSE high-frequency pulse (X5)
The set percentage of PID is directly dependent on the HDI (percentage).
For the details of AI1-AI2 and X5, see the description of F00.04. When used as the PID
setting, the percentage will directly turn the set value, and the maximum output is 100.00%.
F09.00=6: communication setting
The percentage of PID setting depends directly on the communication (percentage).
If the master-slave communication (F10.05=1) is enabled and the inverter works as the
slave (F10.06=0), the specific setting percentage is “700FH (master-slave
communication setting) * F10.08 (slave receiving proportional coefficient)”, and the
700FH data range is -100.00% to 100.00%, as detailed in Table 12-31.
For the general communication (F10.05=0), the specific setting percentage is “7004H
(communication setting of process PID setting)”, and the 7004H data range is
-100.00% to 100.00%, as detailed in Table 12-31.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F09.02 PID feedback source
1: AI1
2: AI2
3: retention
4: retention
5: PULSE, high-frequency
pulse (X5)
6: Communication setting
1
〇
F09.02=1:AI1
F09.02=2: AI2
The PID feedback percentage is directly dependent on the AI (percentage).
For the details of AI1 to AI2, see the description of F00.04. When is used as the PID
feedback, the percentage will directly turn the feedback value, and the maximum output is