User Manual of EM730/EM730E Series Inverter
129
Chapter 7
Function Code Details
7.1
Basic Function Parameter Group of F00 Group
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.01
Drive control
mode of motor 1
0: V/F control (VVF)
1: Speed sensorless vector control
(SVC)
0
〇
F00.01=0: V/F control (VVF)
It is used for one-to-many, fast and low-precision speed control.
F00.01=1: speed sensorless vector control (SVC)
The open-loop vector control is suitable for general high-performance control. An inverter
drives one motor only. It is suitable for machine tools, centrifuges, drawing machines, injection
molding machines and other loads.
1. In order to improve the control performance, self-learning is needed to
obtain the correct motor parameters before vector control.
2. In the vector control mode, the inverter can be used with one motor only,
and the motor capacity should not be greatly different from the inverter capacity;
otherwise, the control performance may decline or the system may not work properly.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.02
Options of
command
source
F00.02=0: keyboard control
(LOC/REM indicator ON)
1: terminal control (LOC/REM
indicator: OFF)
2: communication control
(LOC/REM indicator: flicker)
0
〇
F00.02=0: keyboard control (LOC/REM indicator ON)
The start and stop of the inverter are controlled by the RUN key
, STOP key
on the keyboard. In the case of no trip protection, press the RUN key
to enter the