User Manual of EM730/EM730E Series Inverter
217
0: forward
1: reverse
Tens place:
Acceleration and
deceleration time options
0: acceleration and
deceleration time 1
1: acceleration and
deceleration time 2
2: acceleration and
deceleration time 3
3: acceleration and
deceleration time 4
F08.48
Running time of the
fifteenth segment
0.0 - 6000.0
s/min
5.0
●
When the simple PLC is running, the operating frequency, operating direction,
acceleration/deceleration time and operating time in the entire segment can be set separately.
This is described below with the 13
th
segment (the last segment) as an example. The specific
operation is shown in Fig. 7-.
F08.12=50.00
: the operating frequency of 13
th
segment is 50.00Hz.
F08.43=31
: the operating direction in the 13
th
segment is reverse, and the acceleration and
deceleration are controlled based on the acceleration and deceleration time 4 (F15.07/F15.08).
F08.44=5.0
: the operating time in the 13
th
segment is 5.0s (F08.18=0 by default).
7.10
PID Function Parameter Group of F09 Group
The EM730/EM730E series inverter has a process PID function, as described in this
section. Process PID control is mainly for pressure control, flow control and temperature
control.
Ts
KpKi
Kp
KpKdTs
dt
d
Ref
Fdb
Out
+
+
+
+
Fig. 7-27 Block Diagram of Process PID