![Sinee EM730 Series Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544033.webp)
User Manual of EM730/EM730E Series Inverter
33
will cause damage to the rectifier part of the inverter. In this case, please connect a three-phase
AC reactor (optional) to the input side of the inverter. This will not only suppress the peak
current and voltage, but also improve the power factor of the system.
Installation of surge suppressor
When an inductive load (electromagnetic contactor, solenoid valve, solenoid coil,
electromagnetic circuit breaker, etc.) is connected near the inverter, please install a surge
suppressor.
Installation of noise filter on power supply side
The noise filter is used to suppress the noise that invades the inverter from the power cable,
and the impact of inverter noise on the power grid.
Use a dedicated noise filter for the inverter. Ordinary noise filters do not have
good effects, so they are not used usually.
The correct and incorrect installations of the noise filter are shown in Fig. 3-5 and Fig. 3-6.
MCCB
Dedicated
noise filter
Other
control
devices
EMC
Inverter
IM
Fig.3-5 Correct Installation of Noise Filter