![Sinee EM730 Series Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544054.webp)
User Manual of EM730/EM730E Series Inverter
54
Flicker bit
Flicker bit
Flicker bit
Flicker bit
Fig. 4-5 Function Code Modification in Non-default Mode
4.2.4
Protection information display mode (
--
E
--
)
In the protection information display mode, press the ENTER key to enter the Level 2
menu. The Level 2 menu will only display the fault record group under the F19 group, which is
conducive to direct viewing of protection record information.
Turn the potentiometer key
on the keyboard in the Level 2 menu under this mode to
increase or decrease the function code of the protection group, and the shift key
will be
unavailable. In case of protection, you can press the shift key
on the keyboard in the
Level 3 menu to switch the display of the protection code, protection output frequency,
protection output current, protection bus voltage, and protection operation status.
4.3
Protection Monitoring
When the inverter is in the protection status, you can directly press the right shift key
to switch the current protection type and the output frequency, output current, output
voltage, running status and working time during the protection.
4.4
Operation Monitoring
4.4.1
Normal monitoring
In the monitoring status mode 1 of EM730/EM730E, you can set any function code to be
viewed between F12.33 and F12.37. When F12.32=1, the monitoring mode 1 will be enabled. If
the Level 0 monitoring menu appears, you can press the right shift key
to switch the
monitoring parameters according to the order set for each function code between F12.33 and
F12.37. When the inverter changes from the stop status to running status, the monitoring