User Manual of EM730/EM730E Series Inverter
131
Enable/Disable the terminal RUN to control the start and stop of the inverter, and the
terminal F/R to control the forward/reverse running. If F00.21 is set to 1 and reverse running is
disabled, the F/R terminal will not be available. If the mode of deceleration to stop is selected,
the logic diagram is as shown in Fig. 7-6(b);
F00.03=1: the terminal RUN controls forward running, and the terminal F/R is in the
reverse mode.
Enable/Disable the terminal RUN to control the forward running and stop of the inverter,
and the terminal F/R to control the reverse running and stop. When the terminals RUN and F/R
are enabled simultaneously, the inverter will be stopped. If reverse running is disabled, the
terminal F/R will not be available. If the mode of deceleration to stop is selected, the
forward/reverse logic will be run, as shown in Fig. 7-6(d);
RUN
F/R
COM
24V
Inverter
Operation
Forward/reverse
(a) Wiring diagram of two-line control (F00.03=0) (b) F04.19=0, F00.03=0, run the
forward/reverse logic
(c)
Wiring
diagram
of
two-line
control
(F00.03=1) (d) F04.19=0, F00.03=1: forward/reverse running logic
Fig. 7-6 Two-line Control
When the start/stop value of F00.03 is set to 0 or 1, even if the terminal RUN is
available, the inverter can be stopped by pressing the STOP key
or sending an
external stop command to the terminal. In this case, the inverter will not be in the
Reverse
RUN
F/R
COM
24V
Inverter
Forward
RUN
F/R
f
Output
frequency
-f
Time