User Manual of EM730/EM730E Series Inverter
137
2.
The process PID and simple PLC modules will not be valid until they are
selected.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F00.06
Options of
frequency
source
0: main frequency source A
1: auxiliary frequency source B
2: main and auxiliary operation results
3: switching between main frequency
source A and auxiliary frequency source B
4: switching between main frequency
source A and main and auxiliary operation
results
5: switching between auxiliary frequency
source B and main and auxiliary
operation results
0
〇
Select the final valid frequency setting channel and operation mode.
F00.06=0: main frequency source A
The final set frequency only depends on the main frequency source A.
F00.06=1: auxiliary frequency source B
The final set frequency only depends on the auxiliary frequency source B.
F00.06=2: main and auxiliary operation results
The final set frequency depends on the main and auxiliary operation results. Refer to the
description of the function code F00.08.
F00.06=3: switching between the main frequency source A and auxiliary frequency
source B
The final set frequency is determined by the status of the input function “26: Frequency
source switching”: invalid, depending on the main frequency source A; valid, depending on the
auxiliary frequency source B.
F00.06=4: switching between main frequency source A and main and auxiliary
calculation results
The final set frequency is determined by the status of the input function “26: Frequency
source switching”: invalid, depending on the main frequency source A; valid, depending on the
main and auxiliary operation results. Refer to the description of the function code F00.08.
F00.06=5: switching between the auxiliary frequency source B and main and auxiliary