protection
F07.22
Load loss
detection
level
0.0-100.0
%
20.0
●
F07.23
Load loss
detection
time
0.0 - 60.0
s
1.0
●
F07.24
Options of
load loss
protection
action
0: trip protection, free stop
1: trip protection, stop according to stop mode
2: Continue to run, with DO status output
1
〇
F07.25
Motor
overspeed
detection
level
0.0-50.0 (reference: maximum frequency F00.16)
%
20.0
●
F07.26
Motor
overspeed
detection
time
0.0-60.0, 0.0: disable motor overspeed protection
s
1.0
●
F07.27
AVR
function
0: Invalid
1: valid
2: automatic
1
〇
F07.28
Stall
protection
detection
time
0.0-6000.0(0.0: no stallprotection detection)
s
0.0
〇
F07.29
Stall control
intensity
0 - 100
%
20
〇
F07.30
Instantaneous
stop/no-stop
deceleration
time
0.00 - 300.00
s
20.00
〇
F07.32
Action
option 2 of
protection
E10
E13
E15
E16
*
E19
E20
*
000
00000
〇
0: allow protection retry
1: disable protection retry
F07.34
Action
option 3 of
protection
*
*
*
*
* *
E09
E17
*****00
〇
0: allow protection retry
1: disable protection retry
F08
Multi-segment speed and simple PLC
F08.00
Multi-segme
nt speed 1
0.00 to maximum frequency F00.16
Hz
0.00
●
F08.01
Multi-segme
nt speed 2
0.00 to maximum frequency F00.16
Hz
5.00
●