p29543[0...3]
BI: Multi-pump control motor under repair / Mpc mtr_und_ser
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
[0] 29542.0
[1] 29542.1
[2] 29542.2
[3] 29542.3
Description:
Sets the signal source(digital input or p29542) for service mode.
The signal indicates the motor/motors which is/are under repair or locked manually.
Index:
[0] = motor 1 under repair
[1] = motor 2 under repair
[2] = motor 3 under repair
[3] = motor 4 under repair
r29544
Multi-pump control index of motors under repair / Mpc mtr und repair
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the motors which are interlocked/under repair.
Value:
r29544.0 = 1: Motor 1 is interlocked / under repair
r29544.1 = 1: Motor 2 is interlocked / under repair
r29544.2 = 1: Motor 3 is interlocked / under repair
r29544.3 = 1: Motor 4 is interlocked / under repair
r29545
CO/BO: Multi-pump control bypass command / Mpc bypass cmd
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Dispalys the signal source for the control command to the bypass.It is BiCo to p1266.
Note
The "Bypass" function switches the motor between inverter and line operation.
p29546
Multi-pump control deviation threshold / Mpc devia thres
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
20.00 [%]
Description:
If the system deviation (p2273) at the PID technology controller exceeds the threshold (p29546) and no more motor
is available, alarm A52963 occurs.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
711
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...