Set controller parameters K
P
, T
I
and T
d
.
Procedure
1. Temporarily set the ramp-up and ramp-down times of the ramp-function generator (p2257
and p2258) to zero.
2. Enter a setpoint step and monitor the associated actual value.
The slower the response of the process to be controlled, the longer you must monitor the
controller response. Under certain circumstances (e.g. for a temperature control), you need
to wait several minutes until you can evaluate the controller response.
W
Optimum controller response for applications that do not permit
any overshoot.
The actual value approaches the setpoint without any significant
overshoot.
W
Optimum controller behavior for fast correction and quick com‐
pensation of disturbance components.
The actual value approaches the setpoint and slightly over‐
shoots, maximum 10 % of the setpoint step.
W
The actual value only slowly approaches the setpoint.
● Increase the proportional component K
P
(p2280) and reduce
the integration time T
I
(p2285).
W
The actual value only slowly approaches the setpoint with slight
oscillation.
● Increase the proportional component K
P
(p2280) and reduce
the rate time T
d
(p2274)
W
The actual value quickly approaches the setpoint, but over‐
shoots too much.
● Decrease the proportional component K
P
(p2280) and
increase the integration time T
I
(p2285).
3. Set the ramp-up and ramp-down times of the ramp-function generator back to their original
value.
You have manually set the technology controller.
❒
Limiting the output of the technology controller
In the factory setting, the output of the technology controller is limited to ± maximum speed. You
must change this limit, depending on your particular application.
Example: The output of the technology controller supplies the speed setpoint for a pump. The
pump should only run in the positive direction.
Advanced commissioning
6.5 Technology controller
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
249
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......