r0050.0...1
CO/BO: Command Data Set CDS effective / CDS effective
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8560
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the effective Command Data Set (CDS).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
CDS effective bit 0
ON
OFF
-
01
CDS effective bit 1
ON
OFF
-
Dependency:
See also: p0810, p0811, r0836
Note
The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
r0051.0...1
CO/BO: Drive Data Set DDS effective / DDS effective
Access level: 2
Calculated: -
Data type: Unsigned8
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8565
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the effective Drive Data Set (DDS).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DDS effective bit 0
ON
OFF
-
01
DDS effective bit 1
ON
OFF
-
Dependency:
See also: p0820, p0821, r0837
Note
When selecting the motor data identification routine and the rotating measurement, the drive data set changeover is
suppressed.
r0052.0...15
CO/BO: Status word 1 / ZSW 1
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and connector output for status word 1.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ready for switching on
Yes
No
-
01
Ready
Yes
No
-
02
Operation enabled
Yes
No
-
03
Fault present
Yes
No
-
04
Coast down active (OFF2)
No
Yes
-
05
Quick Stop active (OFF3)
No
Yes
-
06
Switching on inhibited active
Yes
No
-
07
Alarm present
Yes
No
-
08
Deviation setpoint/actual speed
No
Yes
-
09
Control request
Yes
No
-
10
Maximum speed reached
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
364
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......