Suppressing the automatic restart only functions for the setting p1210 = 6, 16 or 26.
Note
Motor starts in spite of an OFF command via the fieldbus
The converter responds with a fault if fieldbus communication is interrupted. For one of the
settings p1210 = 6, 16 or 26, the converter automatically acknowledges the fault and the motor
restarts, even if the higher-level control attempts to send an OFF command to the converter.
● In order to prevent the motor automatically starting when the fieldbus communication fails,
you must enter the fault number of the communication error in parameter p1206.
Parameter
Number
Name
Factory setting
p1206
Automatic restart faults not active
0
p1210
Automatic restart mode
0
p1211
Automatic restart, start attempts
3
p1212
Automatic restart, wait time start attempts
1 s
p1213[0]
Automatic restart monitoring time
for restart
60 s
p1213[1]
Reset automatic restart monitoring time for
start-up counter
0 s
p29630
Activate continuous operation
0
Advanced commissioning
6.8 Drive availability
SINAMICS G120XA converter
322
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......