p2117[0...n]
BI: External alarm 3 / External alarm 3
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for external alarm 3.
Dependency:
See also: A07852
Note
An external alarm is triggered with a 1/0 signal.
p2117[0...n]
BI: External alarm 3 / External alarm 3
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546
Min:
-
Max:
-
Factory setting:
4022.0
Description:
Sets the signal source for external alarm 3.
Dependency:
See also: A07852
Note
An external alarm is triggered with a 1/0 signal.
p2118[0...19]
Change message type message number / Chng type msg_no
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
0
Max:
65535
Factory setting:
0
Description:
Selects faults or alarms for which the message type should be changed.
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
See also: p2119
Note
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
p2119[0...19]
Change message type type / Change type type
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8050, 8075
Min:
1
Max:
3
Factory setting:
1
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
Fault (F)
2:
Alarm (A)
3:
No message (N)
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
See also: p2118
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
581
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......