6.2.2.7
Analog outputs
Function description
$2
*1'
&2U[[\\
S>@
S>@
$2
*1'
&2U[[\\
S>@
S>@
Connector outputs are designated with a "CO” as prefix.
Defining the analog output type
Define the analog output type using parameter p0776.
AO 0
Current output (factory setting)
0 mA … +20 mA
p0776[0] =
0
Voltage output
0 V … +10 V
1
Current output
+4 mA … +20 mA
2
AO 1
Current output (factory setting)
0 mA … +20 mA
p0776[1] =
0
Voltage output
0 V … +10 V
1
Current output
+4 mA … +20 mA
2
Defining the function of an analog output
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the specific analog output via its index,
e.g. parameter p0771[0] is assigned to analog output 0.
Example
$2
U
S>@
To output the converter output current via analog output 0, you must interconnect AO 0 with the
signal for the output current.
Set p0771 = 27.
Parameters
Table 6-6
Frequently used connector outputs (CO) of the converter
Parameter
Description
Factory setting
r0021
CO: Speed actual value, smoothed
- rpm
r0025
CO: Output voltage, smoothed
- Vrms
r0026
CO: DC link voltage, smoothed
- V
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
145
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......