![Siemens SINAMICS G120XA Скачать руководство пользователя страница 662](http://html.mh-extra.com/html/siemens/sinamics-g120xa/sinamics-g120xa_operating-instructions-manual_381566662.webp)
r3996[0...1]
Parameter write inhibit status / Par_write inhib st
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays whether writing to parameters is inhibited.
r3996[0] = 0:
Parameter write not inhibited.
0 < r3996[0] < 100:
Parameter write inhibited. The value shows how the calculations are progressing.
Index:
[0] = Progress calculations
[1] = Cause
Note
For index 1:
Only for internal Siemens troubleshooting.
r4022.0...3
CO/BO: PM330 digital inputs status / PM330 DI status
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status of the digital inputs of the PM330 power unit.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X9.3, external alarm)
High
Low
-
01
DI 1 (X9.4, external fault)
High
Low
-
02
DI 2 (X9.5, Emergency Off category 0)
High
Low
-
03
DI 3 (X9.6, Emergency Off category 1)
High
Low
-
Dependency:
See also: r4023
Note
DI: Digital Input
r4023.0...3
CO/BO: PM330 digital inputs status inverted / PM330 DI stat inv
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the inverted status of the digital inputs of Power Module 330 (PM330).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X9.3, external alarm)
High
Low
-
01
DI 1 (X9.4, external fault)
High
Low
-
02
DI 2 (X9.5, Emergency Off category 0)
High
Low
-
03
DI 3 (X9.6, Emergency Off category 1)
High
Low
-
Dependency:
See also: r4022
Note
DI: Digital Input
Parameters
7.3 Parameters
SINAMICS G120XA converter
660
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......