Description:
Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
6 = synchronous reluctance motor
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the BOP-2/
IOP-2).
The following applies for values < 100:
Motor data must be manually entered.
The following applies for values >= 100:
Motor data are automatically loaded from an internal list.
Value:
0:
No motor
1:
Induction motor
2:
Synchronous motor
6:
Reluctance motor
10:
1LE1 induction motor (not a code number)
13:
1LG6 induction motor (not a code number)
17:
1LA7 induction motor (not a code number)
19:
1LA9 induction motor (not a code number)
100:
1LE1 induction motor
101:
1PC1 induction motor
105:
1LE5 induction motor
108:
1PH8 induction motor
600:
1FP1 synchronous reluctance motor
603:
1FP3 synchronous reluctance motor OEM
Dependency:
When selecting p0300 = 10 ... 19, parameters p0335, p0626, p0627, and p0628 of the thermal motor model are pre-
assigned as a function of p0307 and p0311.
For p0096 = 1 (Standard Drive Control) synchronous motor types cannot be selected.
CAUTION
If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
NOTICE
If a catalog motor is selected (p0300 >= 100) and an associated motor code number (p0301), then the parameters that
are associated with this list cannot be changed (write protection). The write protection is canceled if the motor type
p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 1 for p0301 = 1xxxx). Write protection is
automatically canceled when the results of motor data identification are copied to the motor parameters.
The motor type of a catalog motor corresponds to the upper three digits of the code number or the following
assignment (if the particular motor type is listed):
Type/code number ranges
100 / 100xx, 110xx, 120xx, 130xx, 140xx, 150xx
108 / 108xx, 118xx, 128xx, 138xx, 148xx, 158xx
Note
Once the Control Unit has been switched on for the first time or if the factory settings have been defined accordingly,
the motor type is preconfigured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
Parameters
7.3 Parameters
SINAMICS G120XA converter
388
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......