r3313
Efficiency optimization 2 optimum flux / Optimum flux
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: r2004
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6722, 6837
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Displays the calculated, optimum flux.
Dependency:
See also: p1401, p3315, p3316
Note
The function is activated via p1401.14 = 1.
p3315[0...n]
Efficiency optimization 2 minimum flux limit value / Min flux lim val
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6722, 6837
Min:
10.0 [%]
Max:
200.0 [%]
Factory setting:
50.0 [%]
Description:
Sets the minimal limit value for the calculated optimum flux.
Dependency:
See also: p1401, r3313, p3316
Note
The function is activated via p1401.14 = 1.
p3316[0...n]
Efficiency optimization 2 maximum flux limit value / Max flux lim val
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6722, 6837
Min:
10.0 [%]
Max:
200.0 [%]
Factory setting:
110.0 [%]
Description:
Sets the maximum limit value for the calculated optimum flux.
Dependency:
See also: p1401, r3313, p3315
Note
The function is activated via p1401.14 = 1.
p3320[0...n]
Fluid flow machine power point 1 / Fluid_mach P1
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
25.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 1 as a [%].
The characteristic comprises the following value pairs:
Power (P) / speed (n)
p3320 / p3321 --> point 1 (P1 / n1)
p3322 / p3323 --> point 2 (P2 / n2)
p3324 / p3325 --> point 3 (P3 / n3)
p3326 / p3327 --> point 4 (P4 / n4)
p3328 / p3329 --> point 5 (P5 / n5)
Parameters
7.3 Parameters
SINAMICS G120XA converter
644
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......