p7761
Write protection / Write protection
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Setting for activating/deactivating the write protection for adjustable parameters.
Value:
0:
Deactivate write protection
1:
Activate write protection
Dependency:
See also: r7760
Note
Parameters with the "WRITE_NO_LOCK" attributes are excluded from the write protection.
p7762
Write protection multi-master fieldbus system access behavior / Fieldbus acc_behav
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the behavior for write protection when accessing via multi-master fieldbus systems (e.g. CAN, BACnet).
Value:
0:
Write access independent of p7761
1:
Write access dependent on p7761
Dependency:
See also: r7760, p7761
p7763
KHP OEM exception list number of indices for p7764 / KHP OEM qty p7764
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
1
Max:
500
Factory setting:
1
Description:
Sets the number of parameters for the OEM exception list (p7764[0...n]).
p7764[0...n], with n = p7763 - 1
Dependency:
See also: p7764
Note
KHP: Know-How Protection
Even if know-how protection is set, parameters in this list can be read and written to.
p7764[0...n]
KHP OEM exception list / KHP OEM excep list
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: p7763
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
65535
Factory setting:
[0] 7766
[1...499] 0
Description:
OEM exception list (p7764[0...n] for setting parameters that should be excluded from know-how protection.
p7764[0...n], with n = p7763 - 1
Dependency:
The number of indices depends on p7763.
See also: p7763
Parameters
7.3 Parameters
SINAMICS G120XA converter
666
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......