![Siemens SINAMICS G120XA Скачать руководство пользователя страница 100](http://html.mh-extra.com/html/siemens/sinamics-g120xa/sinamics-g120xa_operating-instructions-manual_381566100.webp)
Note
If terminals 3 to 6 are not used, then you must connect 24 V DC to them. To do this, use an
external power supply or terminal 9 on the Control Unit.
The reference potential is connected to terminal X9.2 and X9.7, and terminal 28 on the Control
Unit.
Note
Line contactor control
If the line contactor is controlled via terminals 11 and 12, then it is not necessary to use a control
transformer to provide isolation from the line supply. A 250 V/8 A fuse must be used as
protection.
Note
Insulated end sleeves
Insulated end sleeves according to DIN 46228-4 must be used.
Note
Strain relief
For strain relief, the cables to the Control Unit and to the terminal X9 must be fastened to the
lugs in the cable duct below terminal X9 (e.g. with cable ties).
If the cables are introduced at the side (at the height of terminal X9), the strain relief must be
provided outside the Power Module.
Terminal Name
Meaning
Input/
output
Technical data
1
P24
External power sup‐
ply
Input
Voltage: 24 V DC (20.1 V ... 28.8 V)
Current consumption: max. 2 A
2
M
Electronics ground
Reference
3
External alert
External alarm
Input
Voltage: -3 V ... +30 V
Current consumption:
● 6.4 mA at 24 V DC
● 1.3 mA at < 5 V
● 4 mA at > 15 V
● 8 mA at 30 V
Level (including ripple):
● High level: 15 V ... 30 V
● Low level: -3 V ... +5 V
4
External fault
External fault
Input
5
Stop 0
Emergency OFF, cat‐
egory 0
Input
6
Stop 1
Emergency Stop, cat‐
egory 1
Input
7
M
Reference
8
DC link charged Enable signal, "U
DC
link
charged"
Output
Voltage: 24 V DC
Max. load current: 500 mA
Continuously short-circuit proof
The output current is taken from the supply at X9, terminal 1.
Wiring
4.2 Control interfaces
SINAMICS G120XA converter
98
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......