Note
For motors, type p0300 = 6 and 6xx, operation with U/f control is only recommended for diagnostic purposes.
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
CUG120XA_USS
(PM330)
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: C2(1), T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6300, 6301,
6851, 8012
Min:
0
Max:
20
Factory setting:
20
Description:
Sets the open and closed-loop control mode of a drive.
Value:
0:
U/f control with linear characteristic
1:
U/f control with linear characteristic and FCC
2:
U/f control with parabolic characteristic
4:
U/f control with linear characteristic and ECO
7:
U/f control for a parabolic characteristic and ECO
20:
Speed control (encoderless)
Dependency:
For Dynamic Drive Control (p0096 = 2), only p1300 = 20 can be set.
Only operation with U/f characteristic is possible if the rated motor speed is not entered (p0311).
See also: p0300, p0311, p0500
NOTICE
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for the
ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note
For motors, type p0300 = 14, operation with U/f control is only recommended for diagnostic purposes.
p1302[0...n]
U/f control configuration / U/f config
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description:
Sets the configuration for the U/f control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
04
Field orientation
Yes
No
-
05
Starting current when accelerating without flux boost
Yes
No
-
07
Inhibit Iq,max controller I component
Yes
No
-
08
Saturation characteristic for the starting current
Yes
No
-
09
Current boost for fast magnetization
Yes
No
-
NOTICE
p1302 bit 5 = 1: (only for field orientation p1302 bit 4 = 1)
This setting is only selected for very fast acceleration.
Parameters
7.3 Parameters
SINAMICS G120XA converter
510
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......