![Siemens SINAMICS G120XA Скачать руководство пользователя страница 864](http://html.mh-extra.com/html/siemens/sinamics-g120xa/sinamics-g120xa_operating-instructions-manual_381566864.webp)
Property
Explanation
Analog outputs
2 (AO 0 ... AO 1) ● Not isolated
● 16-bit resolution
● Switchable between voltage and current via parameter setting
– 0 ... 10 V
– 0/4 ... 20 mA
● Update time: 4 ms
● <400 mV offset at 0 %
Motor temperature sensor PTC
● Short-circuit monitoring < 20 Ω
● Overtemperature 1650 Ω
KTY84
● Short-circuit monitoring < 50 Ω
● Wire-break: > 2120 Ω
Pt1000
● Short-circuit monitoring < 603 Ω
● Wire-break > 2120 Ω
Bimetalic temperature switch with NC contact
Memory card
Slot for SD or MMC memory cards
Recommended memory cards (Page 726)
Technical data
11.1 Technical data of inputs and outputs
SINAMICS G120XA converter
862
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB