NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
r1087
CO: Speed limit negative effective / n_limit neg eff
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050, 7958
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output for the active negative speed limit.
Dependency:
See also: p1082, p1086, p1088
Note
Vector control: r1087 >= -60 x 240 Hz / r0313
p1088[0...n]
CI: Speed limit in negative direction of rotation / n_limit neg
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: p2000
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3050
Min:
-
Max:
-
Factory setting:
1086[0]
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
p1091[0...n]
Skip speed 1 / n_skip 1
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets skip speed 1.
Dependency:
See also: p1092, p1093, p1094, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Note
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
p1092[0...n]
Skip speed 2 / n_skip 2
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets skip speed 2.
Dependency:
See also: p1091, p1093, p1094, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Parameters
7.3 Parameters
SINAMICS G120XA converter
478
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......