Converter
frame size
Terminal/connector type
Cable cross-section
Screw tightening torque
- Nm (lbf.in)
Stripped in‐
sulation
length (mm)
FSH
Line, motor,
PE and DC
link
Cable lug accord‐
ing to DIN 46234
for M12 screws
1)
2 × 240 mm
2
2 ×
500 MCM
50
442.5
--
FSJ
4 × 240 mm
2
4 ×
500 MCM
1)
Alternative copper busbars can be used for line and motor connections. Make sure that you use copper busbars of the same
cross-sections as the connecting busbars of the converter itself (FSH: 60 mm × 6 mm; FSJ 450 kW to 500 kW: 80 mm ×
6 mm; FSJ 560 kW: 80 mm × 8 mm).
4.1.4.4
Cable lugs
For cable connections using cable lugs, the maximum dimensions of the cable lugs are listed
in the table below. These cable lugs are not to exceed these dimensions, as mechanical
fastening and adherence to the voltage distances is not guaranteed otherwise.
D
G
O
F
G
Converter
frame size
Screw/bolt Cable cross-sec‐
tion (mm
2
)
a (mm)
c (mm)
d1 (mm) d (mm)
l (mm)
FSF
M10
120
26
22
10.5
32
59.5
FSG
185
30
27
10.5
39
72.5
FSH/FSJ
M12
240
32
23.5
13
38
56
The cable lugs can be attached as shown in the following diagram if, at one connection per
phase, two cable lugs can be connected.
Wiring
4.1 Line supply and motor
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
73
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......