Table 6-14
Assigning the Modbus registers to the parameters - PID diagnostics
Regis‐
ter
Description
Ac‐
cess
Unit
Scaling
ON/OFF text/
value range
Data / parameter
40520
Effective setpoint acc. to internal tech‐
nology controller MOP ramp-function
generator
R
%
100
-100.0 … 100.0
r2250
40521
Actual value of technology controller af‐
ter filter
R
%
100
-100.0 … 100.0
r2266
40522
Output signal technology controller
R
%
100
-100.0 … 100.0
r2294
Table 6-15
Modbus registers for communication via DS47
Regis‐
ter
Description
Ac‐
cess
Unit
Scaling
Data / parameter
40601
DS47 Control
R/W
--
--
--
40602
DS47 header
R/W
--
--
--
40603
DS47 data 1
R/W
--
--
--
…
…
…
40722
DS47 data 120
R/W
--
--
--
Table 6-16
Modbus registers for multi-pump control
Register Last reg‐
ister
Description
Ac‐
cess
Unit
Scaling
ON/OFF text/value
range
Data / parameter
40800
Status word
R
--
1
0 … 65535
p29529
40801
Motor index speed control
R
--
1
0 … 3
p29538
40802
Status word, service mode
R
--
1
0 … 65535
p29544
40804
40805
Motor 1 operating hours
R/W
h
10
0 … 429496729.5
p29530[0]
40806
40807
Motor 2 operating hours
R/W
h
10
0 … 429496729.5
p29530[1]
40808
40809
Motor 3 operating hours
R/W
h
10
0 … 429496729.5
p29530[2]
40810
40811
Motor 4 operating hours
R/W
h
10
0 … 429496729.5
p29530[3]
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
158
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......