Efficiency optimization, method 1
)OX[VHWSRLQW
7RUTXH
1RORDG
RSHUDWLRQ
5DWHGWRUTXH
3DUWLDOORDGRSHUDWLRQ
Sy
Sy
S
S
S
S
Figure 6-82
Reduce the flux setpoint in the partial load range of the motor
The motor operates in partial load mode between no-load operation and the rated motor torque.
Depending on p1580, in the partial load range, the converter reduces the flux setpoint linearly
with the torque.
)OX[
(IILFLHQF\
S
S
S
Figure 6-83
Qualitative result of efficiency optimization, method 1
The reduced flux in the motor partial load range results in higher efficiency.
Parameters
The converter calculates the parameters for the thermal motor model based on the motor data
that has been set – and the motor data identification.
Table 6-73
Efficiency optimization, method 2
Number
Name
Factory setting
p1401[D]
Flux control configuration
0000 0000 0000
0110 bin
p1570[D]
CO: Flux setpoint
100%
p3315[D]
Efficiency optimization 2 minimum flux limit value
50%
p3316[D]
Efficiency optimization 2 maximum flux limit value
110 %
Table 6-74
Efficiency optimization, method 1
Number
Name
Factory setting
p1570[D]
CO: Flux setpoint
100%
p1580[D]
Efficiency optimization
80%
Advanced commissioning
6.9 Energy saving
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
331
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......