6.7.6.6
Rotation monitoring
Function description
The converter monitors the speed or velocity of a machine component via an electromechanic
or electronic encoder, e.g. a proximity switch. Examples of how the function can be used:
● Drive belt monitoring for fans
● Blocking protection for pumps
The converter checks whether the encoder consistently supplies a 24 V signal during motor
operation. If the encoder signal fails for time p2192, the converter signals fault F07936.
',[
)
S
7
U[ [
S
)
W
W
9
',[
S
Figure 6-73
Function plan and time response of the speed monitoring
Parameters
Number
Name
Factory setting
r0722
CO/BO: CU digital inputs, status
-
p2192[D]
Load monitoring, delay time
10 s
p2193[D]
Load monitoring configuration
1
p3232[C]
BI: Load monitoring, failure detection
1
Further information is provided in the parameter list.