p1002[0...n]
CO: Fixed speed setpoint 2 / n_set_fixed 2
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 2.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1003[0...n]
CO: Fixed speed setpoint 3 / n_set_fixed 3
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 3.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1004[0...n]
CO: Fixed speed setpoint 4 / n_set_fixed 4
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 4.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1005[0...n]
CO: Fixed speed setpoint 5 / n_set_fixed 5
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 5.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Parameters
7.3 Parameters
SINAMICS G120XA converter
462
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......