r0080[0...1]
CO: Torque actual value / Actual torque
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2003
Dynamic index: -
Unit group: 7_1
Unit selection: p0505
Function diagram: 6714, 6799
Min:
- [Nm]
Max:
- [Nm]
Factory setting:
- [Nm]
Description:
Display and connector output for actual torque value.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
Dependency:
See also: r0031, p0045
Note
The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
r0082[0...2]
CO: Active power actual value / P_act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: r2004
Dynamic index: -
Unit group: 14_5
Unit selection: p0505
Function diagram: 6714, 6799
Min:
- [kW]
Max:
- [kW]
Factory setting:
- [kW]
Description:
Displays the instantaneous active power.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency:
See also: r0032
Note
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
r0087
CO: Actual power factor / Cos phi act
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
p0096
Application class / Appl_class
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6019
Min:
0
Max:
2
Factory setting:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
Expert
1:
Standard Drive Control (SDC)
2:
Dynamic Drive Control (DDC)
Parameters
7.3 Parameters
SINAMICS G120XA converter
374
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......