r0070
CO: Actual DC link voltage / Vdc act val
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: 5_2
Unit selection: p0505
Function diagram: 6723, 6724,
6730, 6731, 6799
Min:
- [V]
Max:
- [V]
Factory setting:
- [V]
Description:
Display and connector output for the measured actual value of the DC link voltage.
Dependency:
See also: r0026
NOTICE
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not supplied.
In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
Note
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0071
Maximum output voltage / Voltage max
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: 5_1
Unit selection: p0505
Function diagram: 6301, 6640,
6700, 6722, 6723, 6724, 6725,
6727
Min:
- [Vrms]
Max:
- [Vrms]
Factory setting:
- [Vrms]
Description:
Displays the maximum output voltage.
Dependency:
The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note
As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link voltage.
r0072
CO: Output voltage / U_output
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: 5_1
Unit selection: p0505
Function diagram: 5700, 6730,
6731, 6799
Min:
- [Vrms]
Max:
- [Vrms]
Factory setting:
- [Vrms]
Description:
Display and connector output for the actual output voltage of the power unit.
Dependency:
See also: r0025
Note
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0075
CO: Current setpoint field-generating / Id_set
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: 6_2
Unit selection: p0505
Function diagram: 6700, 6714,
6725
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Parameters
7.3 Parameters
SINAMICS G120XA converter
372
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......