Note
The magnetizing current p0320 for induction motors is reset when quick commissioning is exited with p3900 > 0.
If, for induction motors, the magnetizing current p0320 is changed outside the commissioning phase (p0010 > 0), then
the magnetizing inductance p0360 is changed so that the EMF r0337 remains constant.
p0322[0...n]
Maximum motor speed / Mot n_max
Access level: 1
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1, 3)
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.0 [rpm]
Max:
210000.0 [rpm]
Factory setting:
0.0 [rpm]
Description:
Sets the maximum motor speed.
Dependency:
See also: p1082
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0322 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly.
Note
The parameter has no significance for a value of p0322 = 0.
p0323[0...n]
Maximum motor current / Mot I_max
Access level: 1
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1, 3)
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [Arms]
Max:
20000.00 [Arms]
Factory setting:
0.00 [Arms]
Description:
Sets the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0323 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly.
Note
The parameter has no effect for induction motors.
The parameter has not effect for synchronous motors if a value of 0.0 is entered. The user-selectable current limit is
entered into p0640.
p0325[0...n]
Motor pole position identification current 1st phase / Mot PolID I 1st Ph
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [Arms]
Max:
10000.000 [Arms]
Factory setting:
0.000 [Arms]
Description:
Sets the current for the 1st phase of the two-stage technique for pole position identification routine.
The current of the 2nd phase is set in p0329.
The two-stage technique is selected with p1980 = 4.
Dependency:
See also: p0329, p1980, r1992
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
395
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......