p1082 [rpm]
150*60/r0313
150*60/r0313
150*60/r0313
p1800 [kHz]
4
4
4
For converter FSG with sine-wave filter, operation is only permissible in the vector control
mode.
2.6.4
dv/dt filter plus VPL
A combination of dv/dt filter and a voltage peak limiter (VPL) - dv/dt filter plus VPL - are available
to suppress voltage peaks and enable longer motor cables to be connected.
Maximum permissible motor cable length (Page 64)
When using the dv/dt filter plus VPL, observe the following restrictions:
● The maximum output frequency is 150 Hz.
● The maximum pulse frequency is 4 kHz.
Further details for the functional principle and the application cases are available on the Internet
(
https://support.industry.siemens.com/cs/ww/en/view/109748645
).
Note
dv/dt filters plus VPL are available as optional components for converters of frame sizes FSH
and FSJ.
Article number
Converter variants
dv/dt filter plus VPL
Frame size
Rated power (kW)
Article number
FSH
315
6SL3000-2DE38-4AA0
355
400
FSJ
450
6SL3000-2DE41-4AA0
500
560
2.6.5
Operator panel
An operator panel has been designed to enhance the interface and communications
capabilities of the converter. It can be used to commission, troubleshoot and control the
converter, as well as to back up and transfer the converter settings. The operator panels
(BOP-2 and IOP-2) can be mounted either directly on the converter or in a control cabinet door
using a door mounting kit.
Description
2.6 Optional components
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
35
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......