p1901
Test pulse evaluation configuration / Test puls config
CUG120XA_USS
(PM330)
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Phase short-circuit test pulse active
Yes
No
-
01
Ground fault detection test pulse active
Yes
No
-
02
Test pulse at each pulse enable
Yes
No
-
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart
is deactivated (p1200 = 0).
See also: p0287
Note
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), then it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
For chassis power units, the ground fault is also determined using the summed output current (see p0287).
p1909[0...n]
Motor data identification control word / MotID STW
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 0000
0000 0000 0000 bin
Description:
Sets the configuration for the motor data identification.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Stator inductance estimate no measurement
Yes
No
-
02
Rotor time constant estimate no measurement
Yes
No
-
03
Leakage inductance estimate no measurement
Yes
No
-
05
Determine Tr and Lsig evaluation in the time range
Yes
No
-
06
Activate vibration damping
Yes
No
-
07
Deactivate vibration detection
Yes
No
-
11
Deactivate pulse measurement Lq Ld
Yes
No
-
12
Deactivate rotor resistance Rr measurement
Yes
No
-
14
Deactivate valve interlocking time measurement
Yes
No
-
15
Determine only stator resistance, valve voltage fault, dead
time
Yes
No
-
16
Short motor identification (lower quality)
Yes
No
-
17
Measurement without control parameter calculation
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
543
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......