Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2138.7...15
CO/BO: Control word faults/alarms / STW fault/alarm
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2546
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the control word of faults and alarms.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
07
Acknowledge fault
Yes
No
8060
10
External alarm 1 (A07850) effective
Yes
No
8065
11
External alarm 2 (A07851) effective
Yes
No
8065
12
External alarm 3 (A07852) effective
Yes
No
8065
13
External fault 1 (F07860) effective
Yes
No
8060
14
External fault 2 (F07861) effective
Yes
No
8060
15
External fault 3 (F07862) effective
Yes
No
8060
Dependency:
See also: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
r2139.0...15
CO/BO: Status word faults/alarms 1 / ZSW fault/alarm 1
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2548
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for status word 1 of faults and alarms.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Being acknowledged
Yes
No
-
01
Acknowledgment required
Yes
No
-
03
Fault present
Yes
No
8060
06
Internal message 1 present
Yes
No
-
07
Alarm present
Yes
No
8065
08
Internal message 2 present
Yes
No
-
11
Alarm class bit 0
High
Low
-
12
Alarm class bit 1
High
Low
-
13
Maintenance required
Yes
No
-
14
Maintenance urgently required
Yes
No
-
15
Fault gone/can be acknowledged
Yes
No
-
Note
For bit 03, 07:
These bits are set if at least one fault/alarm occurs. Data is entered into the fault/alarm buffer with delay. This is the
reason that the fault/alarm buffer should only be read if, after "fault present" or "alarm present" has occurred, a change
in the buffer was also detected (r0944, r9744, r2121).
For bit 06, 08:
These status bits are used for internal diagnostic purposes only.
For bits 11, 12:
These status bits are used for the classification of internal alarm classes and are intended for diagnostic purposes only
on certain automation systems with integrated SINAMICS functionality.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
587
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......