Description:
Sets the signal source for the setpoint 1 of the technology controller.
Dependency:
See also: p2254, p2255
p2254[0...n]
CI: Technology controller setpoint 2 / Tec_ctrl setp 2
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for the setpoint 2 of the technology controller.
Dependency:
See also: p2253, p2256
p2255
Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the scaling for the setpoint 1 of the technology controller.
Dependency:
See also: p2253
p2256
Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the scaling for the setpoint 2 of the technology controller.
Dependency:
See also: p2254
p2257
Technology controller ramp-up time / Tec_ctrl t_ramp-up
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-up time of the technology controller.
Dependency:
See also: p2258
Note
The ramp-up time is referred to 100 %.
p2258
Technology controller ramp-down time / Tec_ctrl t_ramp-dn
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-down time of the technology controller.
Parameters
7.3 Parameters
SINAMICS G120XA converter
612
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......