controllers keep the motor flux constant using the output voltage, and adjust the matching
current component I
q
in the motor.
Settings that are required
Restart quick commissioning and select the vector control in quick commissioning.
Commissioning (Page 103)
In order to achieve a satisfactory control response, as a minimum you must set the partial
functions – shown with gray background in the diagram above – to match your particular
application:
● Motor and current model: In the quick commissioning, correctly set the motor data on the
rating plate corresponding to the connection type (Y/Δ), and carry out the motor data
identification routine at standstill.
● Speed limits and torque limits: In the quick commissioning, set the maximum speed (p1082)
and current limit (p0640) to match your particular application. When exiting quick
commissioning, the converter calculates the torque and power limits corresponding to the
current limit. The actual torque limits are obtained from the converted current and power
limits and the set torque limits.
● Speed controller: Start the rotating measurement of the motor data identification. You must
manually optimize the controller if the rotating measurement is not possible.
Advanced commissioning
6.6 Motor control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
289
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......