p1274[0...1]
Bypass switch monitoring time / Switch t_monit
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [ms]
Max:
5000 [ms]
Factory setting:
1000 [ms]
Description:
Sets the monitoring time for the bypass switch.
Index:
[0] = Switch motor/drive
[1] = Switch motor/line supply
Dependency:
The "Bypass" function is only available for induction motors.
Note
The monitoring is deactivated with p1274 = 0 ms.
The changeover time for the bypass (p1262) is extended by the value in this parameter.
p1280[0...n]
Vdc controller configuration (U/f) / Vdc_ctr config U/f
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6300, 6320,
6854
Min:
0
Max:
3
Factory setting:
1
Description:
Sets the configuration of the controller for the DC link voltage (Vdc controller) in the U/f operating mode.
Value:
0:
Inhibit Vdc ctrl
1:
Enable Vdc_max controller
2:
Enable Vdc_min controller (kinetic buffering)
3:
Enable Vdc_min controller and Vdc_max controller
Note
For high input voltages (p0210), the following settings can improve the degree of ruggedness of the Vdc_max controller:
- set the input voltage as low as possible, and in so doing, avoid A07401 (p0210).
- set the rounding times (p1130, p1136).
- increase the ramp-down times (p1121).
- reduce the integral time of the controller (p1291), factor 0.5.
- activate the Vdc correction in the current controller (p1810.1 = 1) or reduce the derivative action time of the controller
(p1292, factor 0.5).
In this case, we generally recommend to use vector control (p1300 = 20) (Vdc controller, see p1240).
The following measures are suitable to improve the Vdc_min controller:
- Optimize the Vdc_min controller (see p1287).
- Activate the Vdc correction in the current controller (p1810.1 = 1).
p1281[0...n]
Vdc controller configuration / Vdc ctrl config
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the configuration for the DC link voltage controller.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Vdc min control (U/f) without up ramp
Yes
No
-
02
Vdc min shorter wait time when the line returns
Yes
No
-
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
505
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......