p1093[0...n]
Skip speed 3 / n_skip 3
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets skip speed 3.
Dependency:
See also: p1091, p1092, p1094, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1094[0...n]
Skip speed 4 / n_skip 4
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets skip speed 4.
Dependency:
See also: p1091, p1092, p1093, p1101
NOTICE
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1098[0...n]
CI: Skip speed scaling / n_skip scal
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3050
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for scaling the skip speeds.
Dependency:
See also: p1091, p1092, p1093, p1094
r1099.0
CO/BO: Skip band status word / Skip band ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the skip bands.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
r1170 within the skip band
Yes
No
3050
Dependency:
See also: r1170
Note
For bit 00:
With the bit set, the setpoint speed is within the skip band after the ramp-function generator (r1170).
The signal can be used to switch over the drive data set (DDS).
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
479
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......