p2179[0...n]
Output load identification current limit / Outp_ld iden I_lim
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2002
Dynamic index: DDS, p0180
Unit group: 6_2
Unit selection: p0505
Function diagram: 8022
Min:
0.00 [Arms]
Max:
1000.00 [Arms]
Factory setting:
0.00 [Arms]
Description:
Sets the current limit for output load identification.
A missing output load is displayed using the "Output load not available" message (r2197.11 = 1).
This message is output with a delay time (p2180).
Dependency:
See also: p2180
NOTICE
For synchronous motors the output current can be almost zero under no load conditions.
Note
Missing output load is signaled in the following cases:
- the motor is not connected.
- a phase failure has occurred.
p2180[0...n]
Output load detection delay time / Out_load det t_del
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8022
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
2000 [ms]
Description:
Sets the delay time for the message "output load not available" (r2197.11 = 1).
Dependency:
See also: p2179
p2181[0...n]
Load monitoring response / Load monit resp
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8013
Min:
0
Max:
8
Factory setting:
0
Description:
Sets the response when evaluating the load monitoring.
Value:
0:
Load monitoring disabled
1:
A07920 for torque/speed too low
2:
A07921 for torque/speed too high
3:
A07922 for torque/speed out of tolerance
4:
F07923 for torque/speed too low
5:
F07924 for torque/speed too high
6:
F07925 for torque/speed out of tolerance
7:
Pump/fan load monitoring as alarm
8:
Pump/fan load monitoring as fault
Dependency:
See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, p2193, r2198, p3230, p3231
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925
Parameters
7.3 Parameters
SINAMICS G120XA converter
596
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......