DANGER
It must be absolutely ensured that the system is in a safe condition.
The memory card/device memory of the Control Unit must not be accessed.
Note
If value = 1:
Reset is immediately executed and communications interrupted.
After communications have been established, check the reset operation (refer below).
If value = 2:
Help to check the reset operation.
Firstly, set p0972 = 2 and then read back. Secondly, set p0972 = 1 (it is possible that this request is possibly no longer
acknowledged). The communication is then interrupted.
After communications have been established, check the reset operation (refer below).
If value = 3:
The reset is executed after interrupting cyclic communication. This setting is used to implement a synchronized reset
by a control for several drive units.
If cyclic communication is not active, then the reset is immediately executed.
After communications have been established, check the reset operation (refer below).
To check the reset operation:
After the drive unit has been restarted and communications have been established, read p0972 and check the following:
p0972 = 0? --> the reset was successfully executed.
p0972 = 0? --> the reset was not executed.
p1000[0...n]
Speed setpoint selection / n_set sel
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
200
Factory setting:
2
Description:
Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
1:
Motorized potentiometer
2:
Analog setpoint
3:
Fixed speed setpoint
6:
Fieldbus
7:
Analog setpoint 2
10:
Motor potenti no main setpoint
11:
Motor potenti motor potentiometer
12:
Motor potenti analog setpoint
13:
Motor potenti fixed speed setpoint
16:
Motor potenti fieldbus
17:
Motor potenti analog setpoint 2
20:
Analog se no main setpoint
21:
Analog se motor potentiometer
Parameters
7.3 Parameters
SINAMICS G120XA converter
460
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......