Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification.
Example:
F12345 and fault response = NONE (OFF1, OFF2)
--> The fault response NONE can be changed to OFF1 or OFF2.
For value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
For value = 2 (OFF2):
Internal/external pulse inhibit.
For value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
For value = 5 (STOP2):
n_set = 0
For value = 6 (armature short-circuit, internal/DC braking):
This value can only be set for all drive data sets when p1231 = 4.
a) DC braking is not possible for synchronous motors.
b) DC braking is possible for induction motors.
p2103[0...n]
BI: 1st acknowledge faults / 1st acknowledge
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2441, 2442,
2443, 2447, 2475, 2546, 9220,
9677, 9678
Min:
-
Max:
-
Factory setting:
722.5
Description:
Sets the first signal source to acknowledge faults.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
A fault acknowledgment is triggered with a 0/1 signal.
p2104[0...n]
BI: 2nd acknowledge faults / 2nd acknowledge
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2546, 8060
Min:
-
Max:
-
Factory setting:
[0] 722.5
[1] 722.5
[2] 0
[3] 0
Description:
Sets the second signal source to acknowledge faults.
Note
A fault acknowledgment is triggered with a 0/1 signal.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
577
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......