Note
The maximum and minimum possible pulse frequency is also determined by the power unit being used (minimum pulse
frequency: 2 kHz or 4 kHz).
When the pulse frequency is increased, depending on the particular power unit, the maximum output current can be
reduced (derating, refer to r0067).
If a sine-wave filter is parameterized as output filter (p0230 = 3), then the pulse frequency cannot be set below the
minimum value required for the filter.
For operation with output reactors, the pulse frequency is limited to 4 kHz (see p0230).
If p1800 is changed during commissioning (p0010 > 0), then it is possible that the old value will no longer be able to be
set. The reason for this is that the dynamic limits of p1800 have been changed by a parameter that was set when the
drive was commissioned (e.g. p1082).
The pulse frequency cannot be changed when the motor data identification is activated.
p1800[0...n]
Pulse frequency setpoint / Pulse freq setp
CUG120XA_USS
(PM330)
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8021
Min:
0.500 [kHz]
Max:
4.000 [kHz]
Factory setting:
4.000 [kHz]
Description:
Sets the drive converter switching frequency.
This parameter is pre-set to twice the rated converter value when the drive is first commissioned.
Dependency:
Minimum pulse frequency: p1800 >= 12 * p1082 * r0313 / 60
See also: p0230
Note
The maximum and minimum possible pulse frequency is also determined by the power unit being used (minimum pulse
frequency: 2 kHz or 4 kHz).
When the pulse frequency is increased, depending on the particular power unit, the maximum output current can be
reduced (derating, refer to r0067).
If a sine-wave filter is parameterized as output filter (p0230 = 3), then the pulse frequency cannot be set below the
minimum value required for the filter.
For operation with output reactors, the pulse frequency is limited to 4 kHz (see p0230).
If p1800 is changed during commissioning (p0010 > 0), then it is possible that the old value will no longer be able to be
set. The reason for this is that the dynamic limits of p1800 have been changed by a parameter that was set when the
drive was commissioned (e.g. p1082).
The pulse frequency cannot be changed when the motor data identification is activated.
r1801[0...1]
CO: Pulse frequency / Pulse frequency
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [kHz]
Max:
- [kHz]
Factory setting:
- [kHz]
Description:
Display and connector output for the actual converter switching frequency.
Index:
[0] = Actual
[1] = Modulator minimum value
Note
The selected pulse frequency (p1800) may be reduced if the drive converter has an overload condition (p0290).
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
537
Содержание SINAMICS G120XA
Страница 2: ......
Страница 12: ...Table of contents SINAMICS G120XA converter 10 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 104: ...Wiring 4 2 Control interfaces SINAMICS G120XA converter 102 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 916: ...Index SINAMICS G120XA converter 914 Operating Instructions 03 2019 FW V1 0 A5E44751205B AB ...
Страница 917: ......